10. Electrical characteristics
Model name AOYG07KGCA AOYG09KGCA AOYG12KGCA AOYG14KGCA
Power
supply
Voltage V 230 ~
Frequency Hz 50
Max operating current *1 A 9.0 10.5
Starting current A 2.8 3.5 4.8 6.4
Wiring
spec. *2
Circuit breaker current A 15
Power cable
mm
2
1.5
Connection cable *3
mm
2
1.5
Limited wiring length m 21
*1: Maximum current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appropri-
ate devices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor
size.
DESIGN & TECHNICAL MANUAL
- 58 -
OUTDOOR UNIT
AOYG07-14KGCA