2-1. External input
With using external input function, some functions on this product can be controlled from an external
device.
“Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit.
A twisted pair cable should be used. Maximum length of cable is 150 m.
Use an external input and output cable with appropriate external dimension, depending on the
number of cables to be installed.
The wire connection should be separate from the power cable line.
¢
Indoor unit
Indoor unit functions such as Operation/Stop can be done by using indoor unit connectors.
1
2
3

CN46
PCB
Connected device
*1: The switch can be used on the following condition: DC 12 V to 24 V, 1 mA to 15 mA.
2-1. External input - (05-10) - 2. External input and output
FIELD
WORKING
FIELD
WORKING