EasyManuals Logo

Fujitsu ASYG12LMCE Service Instruction

Fujitsu ASYG12LMCE
61 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #4 background imageLoading...
Page #4 background image
( Fig.1 : Outdoor temperature zone )
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
Minimum
frequency
Maximum
frequency
Maximum
frequency
07/09
12/14
22rps 76rps
18rps
80rps
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Indoor fan mode
Me Lo Quiet
A zone 79rps 61rps 52rps 37rps
B zone 79rps 61rps 52rps 37rps
C zone 79rps 61rps 52rps 37rps
07/09
D zone 64rps 55rps 49rps 36rps
E zone 64rps 55rps 49rps 36rps
F zone 64rps 55rps 49rps 36rps
( Table 1 : Compressor frequency range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +2°C to -2.5°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
12
A zone 96rps 61rps 51rps 33rps
B zone 96rps 61rps 51rps 33rps
C zone 96rps 61rps 51rps 33rps
D zone 68rps 54rps 48rps 33rps
E zone 68rps 54rps 48rps 33rps
F zone 68rps 54rps 48rps 33rps
Outdoor
temperature drops
Outdoor
temperature rises
( Table 2 : Limit of maximum speed based on outdoor temperature )
79rps
96rps
Outdoor
temp. zone
Hi
* If the room temperature is 2°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .
14
A zone 96rps 61rps 51rps 33rps
B zone 96rps 61rps 51rps 33rps
C zone 96rps 61rps 51rps 33rps
D zone 73rps 48ps 36rps 27rps
E zone 73ps 48rps 36rps 27rps
F zone
73rps 48rps 36rps 27rps
Model
Model

Other manuals for Fujitsu ASYG12LMCE

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG12LMCE and is the answer not in the manual?

Fujitsu ASYG12LMCE Specifications

General IconGeneral
TypeAir conditioner indoor unit
Multi-split-
Product colorWhite
Inverter technologyYes
Refrigerating mediumR410A
Air conditioner functionsCooling, Dehumidifying, Heating
Refrigerating medium weight850 g
Cooling capacity in watts (nominal)- W
Operating temperature (cooling) (T-T)-10 - 43 °C
Operating temperature (heating) (T-T)-15 - 24 °C
Airflow750 m³/h
Outdoor unit noise level- dB
Indoor unit typeWall-mountable
Indoor unit depth204 mm
Indoor unit width870 mm
Indoor unit height270 mm
Indoor unit weight8500 g
Indoor unit noise level (high speed)43 dB
AC input voltage230 V
AC input frequency50 Hz
Design load (cooling)- kW
Energy efficiency class (cooling)A++
Hourly energy consumption (cooling)- kWh

Related product manuals