03-02
(          Factory setting)
Setting Description
Function Number Setting Value
No
Yes
42
00
01
1-5. Indoor room temperature sensor switching function
       (Only for Wired remote controller)
The following settings are needed when use the control by 
Wired remote controller temperature sensor.
(          Factory setting)
Setting Description
Function Number Setting Value
A
B
C
D
44
00
01
02
03
1-6. Remote controller signal code
Change the indoor unit Signal Code, depending on the remote controllers.
(          Factory setting)
Setting Description
Function Number Setting Value
Operation/Stop mode
(Setting forbidden)
Forced stop mode
46
00
01
02
1-7. External input control
"Operation/Stop" mode or "Forced stop" mode can be elected.
(          Factory setting)
Setting Description
Function Number Setting Value
No
Yes
49
00
01
1-8. Indoor unit fan control for energy saving
Enable or disable indoor unit fan control when the outdoor unit is stopped.
* If setting value is "00" : Room temperature is controlled by the indoor unit temperature sensor.
* If setting value is "01" : Room temperature is controlled by either indoor unit temperature sensor 
                                        or remote controller unit sensor.
* If setting value is "00" : When the outdoor unit is stopped, the indoor unit fan operates following the 
                                        setting on the remote controller continuously.
* If setting value is "01" : When the outdoor unit is stopped, the indoor unit fan operates at very low speed 
                                        intermittently.