( Fig.1 : Outdoor temperature zone )
1. COOLING OPERATION
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive
difference or variation between a set temperature and present room temperature, and
controls the operation frequency of the compressor.
Minimum
frequency
Maximum
frequency
Maximum
frequency
14rps
60rps
64rps
84rps
90rps
14rps
12rps
90rps
89rps
78rps
77rps
36°C
A zone
34°C
32°C
B zone
30°C
21°C
C zone
19°C
D zone
Indoor fan mode
Me Lo Quiet
A zone 84rps 49rps 36rps 24rps
B zone 84rps 49rps 36rps 24rps
C zone 84rps 49rps 36rps 24rps
D zone 60rps 44rps 34rps 22rps
E zone 60rps 44rps 34rps 22rps
F zone 60rps 44rps 34rps 22rps
( Table 1 : Compressor frequency range )
01-01
E zone
F zone
10°C
0°C
12°C
2°C
* When the room temperature is between +6°C to -1°C of the setting temperature,
the compressor frequency is controlled within the range shown in Table1.
However, the maximum frequency is limited in the range shown in Fig.1 based on the indoor
fan mode and the outdoor temperature.
* If the room temperature is some degrees lower than a set temperature,
the compressor will be stopped.
AO*G09KMTA
AO*G12KMTA
AO*G14KMTA
A zone 90rps 52rps 36rps 24rps
B zone 90rps 52rps 36rps 24rps
C zone 90rps 52rps 36rps 24rps
D zone 64rps 46rps 34rps 22ps
E zone 64rps 46rps 34rps 22rps
F zone 64rps 46rps 34rps 22rps
A zone 89rps 44rps 34rps 22rps
B zone 89rps 44rps 34rps 22rps
C zone 89rps 34rps 22rps
D zone 62rps 40rps 32rps 20rps
E zone 62rps 40rps 32rps 20rps
F zone 62rps 40rps 32rps 20rps
44rps
Outdoor
temperature
Outdoor
temperature
( Table 2 : Limit of maximum speed based on outdoor temperature )
AO*G07KMTA
AO*G09KMTA
AO*G07KMTA
AO*G12KMTA
AO*G14KMTA
Outdoor
temp. zone
Hi
* If the room temperature is 6°C higher than a set temperature, the compressor operation
frequency will attain to maximum performance.
When the compressor operates for 30 minutes continuously at over the maximum frequency ,
the maximum frequency is changed from Maximum Frequency to Maximum Frequency .

Other manuals for Fujitsu ASYG14KMTA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG14KMTA and is the answer not in the manual?

Fujitsu ASYG14KMTA Specifications

General IconGeneral
BrandFujitsu
ModelASYG14KMTA
CategoryAir Conditioner
LanguageEnglish

Related product manuals