5. INDOOR FAN CONTROL
The airflow can be switched in 5 steps such as Auto, Quiet, Lo, Me, Hi, while the indoor fan only runs.
When fan mode is set at [Auto], it operates on [Me] fan Speed.
01-05
2. FAN OPERATION
3. COOLING OPERATION
Switch the airflow [Auto], and the indoor fan motor will run according to a room temperature,
as shown in Fig4.
On the other hand, if switched in [Hi] [Quiet], the indoor motor will run at a constant airflow of [Cool]
operation modes Quiet, Lo, Me, Hi, as shown in Table 5.
( Fig.4 : Airflow change - over ( Cooling : Auto ) )
When the room
temperature rises
When the room
temperature drops
TR : Room temperature
Ts : Setting temperature
TR-Ts > 2°C
1°C > TR-Ts
2°C > TR-Ts > 1°C
=
TR-Ts > 2.5°C
=
1.5°C > TR-Ts
2.5°C > TR-Ts > 1.5°C
=
Hi mode
Me mode
Lo mode
1. Fan speed
( Table 5 : Indoor fan speed )
Operation mode Air flow mode
Speed (rpm)
Cooling/ Fan
Heating
Dry
X zone: 550
J zone: 550
X zone: 550
J zone: 550
X zone: 550
J zone: 550
AS*G07KMTA AS*G09KMTA AS*G12KMTA
4. DRY OPERATION
Refer to the Table 5.
During the dry mode operation, the fan speed setting can not be changed.
AS*G14KMTA
X zone: 580
J zone: 580
Hi
Hi
Me+
Me
Me
Lo
Lo
Quiet
Quiet
Soft Quiet
S-Lo
Cool air prevention
Powerful
Powerful
1210
1140
1040
950
800
630
470 470 470 510
550
400
1050
900
760
550
1120
1250
1180
1040
970
810
630
550
400
1110
920
760
550
1180
1270
1200
1100
1030
880
630
550
400
1110
920
760
550
1180
1360
1290
1160
1100
910
670
580
470
1250
1020
810
580
1320
*Note, during Economy operation and operation mode is Fan, air flow is 1 step downs.
(Hi > Me, Me > Lo, Lo > Quiet, Quiet > Soft Quiet)