EasyManua.ls Logo

Fujitsu ASYG14KMTA - Page 84

Fujitsu ASYG14KMTA
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Detective Actuators:
Detective details:
Forecast of Cause :
Check Point 2 : Check connection of around the Compressor components
OKOK
OKOK
Check Point 3: Replace Main PCB
Outdoor unit Main PCB
Compressor
1. Defective connection of electric components 2. Main PCB failure 3. Compressor failure
If Check Point 1,2 do not improve the symptom, change Main PCB.
Check if connector is removed.
Check erroneous connection.
Check if cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
(Refer to PARTS INFORMATION 2)
For Compressor Terminal, Main PCB
If the detected rotor location is out of phase with actual rotor location
more than 90°, the compressor stops.
After the compressor restarts, if the same operation is repeated
within 40sec, the compressor stops again.
If and repeats 5 times, the compressor stops permanently.
02-23
Check Point 1 : Check Noise from Compressor
Turn on Power and check operation noise.
If an abnormal noise show, replace Compressor.
OKOK
Check Point 4: Replace Compressor
If Check Point 3 do not improve the symptom, change Compressor.
Trouble shooting 20
OUTDOOR UNIT Error Method:
Compressor Control Error
Indicate or Display:
Outdoor Unit : No indication
Indoor Unit : Operation lamp: 9 time Flash, Timer lamp: 5 time Flash
Economy lamp: Continuous flash.
ERROR CODE : [E : 95 ]