Fujitsu AUXB12GA* H - SERVICE INFORMATION Network Communication Abnormal

Fujitsu AUXB12GA* H
241 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Outdoor unit1
(Master unit)
Refrigerant piping
Transmission
Outdoor unit 2
(Slave unit 1)
Outdoor unit 3
(Slave unit 1)
Transmission
Transmission Transmission
Transmission
Transmission
Terminal -
Resistance
53 Ohm
< Main PCB >
-SET 5-4:ON-
TransmissionTransmission
- Basic trouble shooting procedure -
1. Check Error code in one network segment separately, and check the Error code of (OU, IU, RC, ST)
< If the system has more than 2 Net work segments, disconnect the other Network segment.>
2. Connect Service tool to the Outdoor unit, and try out "Address checker" Function by the Service tool.
< Check missing indoor unit or outdoor unit by using Address checker function of Service tool>
3. Check terminal resistance value 53 Ohm + 5% + Line Resistance on the terminal board one by one.
< Terminal Resistance is located on the Outdoor unit PCB(activated SET 5-4 ON) >
*Refer to the wiring diagram of Networlk cable
To other refrigerant circuit
Outdoor unit
A
Measurement
Terminal Resistance A
Measurement
Terminal Resistance A
Measurement
Terminal Resistance A
Measurement
Terminal Resistance A
4-3 SERVICE INFORMATION
SERVICE INFORMATION
Network communication Abnormal
Indoor Unit
Indoor unit 4
Indoor unit 3
Indoor unit 2
Indoor unit 1
Terminal Resistance A is located on the controller PCB of Outdoor unit as the Network for Indoor unit.
-
Example
04-100