01-22
1-8 Field Setting / Function Setting for Outdoor air unit
Setting Mode
ITEM
CODE No.
Setting Function
Default
Indoor unit field setting
Address
setting by
remote controller
01 Indoor unit address 00~63 00~63 00
02 Refrigerant circuit address 00~99 00~99 00
Filter 11 Filter indicator Interval 00 Default
01
Longer
02 Shorter
13 Filter sign display 00 Enable
01 Disable
02 Display only on central remote control
Airflow
Change of
Function 1
40 Auto restart *1 00 Enable
01 Disable
43 Cool air prevention 00 Super low
01 Follow the setting on the remote controller
46 External control 00 Start / Stop
01 Emergency stop
47 Error report target
63 Humidifier control *2
00 All
01 Display only for central remote control
ITEM
CODE No.
Classification
26
05
06
07
08
09
10
11
12
13
14
15
16
17
18
19
20
21
22
31
SP mode 05
SP mode 06
SP mode 07
SP mode 08
SP mode 09
SP mode 10
SP mode 11
SP mode 12
SP mode 13
SP mode 14
SP mode 15
SP mode 16
SP mode 17
SP mode 18
SP mode 19
SP mode 20
SP mode 21
SP mode 22
Normal SP
Static Pressure setting
- Outdoor air unit Only -
The Range of static pressure is
different from one model to other.
02
Foreced stop (Start/Stop by RC is restricted)
00
01
02
mode 00
mode 01
mode 02
*1: Auto restart is an emargency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Select control conditions of external output.
"Mode 00" is output when heating thermostat is ON, "Mode 01" is output in heating operation, "Mode 02" is output in heating operation and in fan operation.
Model name
ARXH054GTAH
ARQH140GTAH
ARXH072GTAH
ARQH224GTAH
ARXH096GTAH
ARQH280GTAH
Range of static
pressure
SP mode 05 to 19
(50 to 185 Pa)
SP mode 05 to 20
(50 to 200 Pa)
SP mode 05 to 22
(50 to 220 Pa)
Normal static
pressure
185 Pa
200 Pa
200 Pa