1-7 Field Setting / Function Setting for Indoor unit
Setting Mode
ITEM
CODE No.
Setting Function
Default
Indoor unit field setting
setting by
remote controller
Address
01 Indoor unit address 00~63 00~63 00
02 Refrigerant circuit address 00~99 00~99 00
Filter 11 Filter indicator Interval 00 Default
01
Longer
02 Shorter
13 Filter sign display 00 Enable
01 Disable
02 Display only on central remote control
Airflow 20 Ceiling airflow 00 Default
(Cassette type only) 01 High ceiling
23 Vertical airflow direction 00 Default
01 Raise
24 Horizontal swing airflow direction 00 Default
01 Left half
02 Right half
Correction 30
Cool air temperature trigger
00 Default (0
°C
)
01 Temperature overshoot setting (+2
°C)
02 Temperature undershoot setting (-2
°C)
31 Heat air temperature trigger 00 Default (0
°C
)
01 Temperature undershoot setting (-6
°C)
02 Temperature slightly undershoot setting (-4
°C)
03 Temperature overshoot setting (+4
°C)
Change of 40 Auto restart *1 00 Enable
01 Disable
43 Cool air prevention 00 Super low
01 Follow the setting on the remote controller
46 External control 00 Start / Stop
01 Emergency stop
47 Error report target 00 All
01 Display only for central remote control
ITEM
CODE No.
Function 1
Classification
26
32
00
01
02
03
04
05
06
07
08
09
31
0 Pa
10 Pa
20 Pa
30 Pa
40 Pa
50 Pa
60 Pa
70 Pa
80 Pa
90 Pa
25 Pa (Standard)
Static Pressure setting
- Slim Duct Only -
The Range of static pressure is
different from one model to other.
Temperature correction in Auto
00
01
Disable
Enable (Nonfunctional on J2 Series)
02 Foreced stop (Start/Stop by RC is restricted)
49 FAN Setting when cooling thermo-
stat OFF *2
01
00
Follow the setting on the remote controller
Foreced stop
*1: Auto restart is an emargency function such as for power failure etc.
Do not start and stop the indoor unit by this function in normal operation.
Be sure to operate by the control unit, converter or external input device.
*2: Fan Setting when cooling thermostat OFF, Connection of the wired remote controller (2-wire type or 3-wire type) and switching its thermistor are necessary.
Model name Range of static pressure
ARXD04
ARXD18
ARXD07/09/12/14 0 to 90 Pa
ARXD24 0 to 50 Pa