SERVICE PARTS INFORMATION 10
Resistor, Cement
Check Point 1 : Appearance check
Check Point 2 : Electric check
Set the tester to the "Resistance" mode, and measure the resistance value between the terminals.
(No polarity)
Judge the result of as follows:
5.6 + 5%
Other than the above
Normal
Deteriorated, defective
No fissures, breaks, damage, etc. at the body and terminals section?
1. Surge prevention resistor (connected to magnetic contactor)
Set the tester to the "Resistance" mode, and measure the
resistance value between the terminals. (No polarity)
Judge the result of as follows:
2. Discharge resistor (connected to electrolytic capacitor)
04-114
-
33 k + 5%
Other than the above
Normal
Deteriorated, defective
-