AC AC
SOLENOIDE COIL SOLENOIDE COIL
Comp. OFF
or Discharge temp. < 50°F(10°C)
or Discharge temp. - High pressure saturated temp. < 41°F(5°C)
Comp. ON
and Discharge temp. > 50°F(10°C)
and Discharge temp. - High pressure saturated temp. > 46.4°F(8°C)
Check Point 4-2 : Check operation of SV3
Check the operation noise when the connector of SV3 is removed.
- When SV3 is open
The sound of operation noise is heard ---> Normal
The sound of operation noise is not heard. ---> Replace SV3
- When SV3 is closed
The sound of operation noise is heard ---> Replace Main PCB
The sound of operation noise is not heard. ---> Normal
=
=
04-121
Pipe (In)
Pipe (Out)
Pipe (In)
Pipe (Out)
OPEN