< Operating state of each part during defrosting operation >
[ STEP 1 ]
02-13
[ STEP 2 ]
[ STEP 3 ]
Compressor
Heat Ex(4WV)
FAN
EEV1
EEV2
EEV3
SV1,SV2
All compressor operaiotn Stop
Change Condensor (OFF)
Stops
0 pls
0 pls
Open (Balancing)
All compressor start
Condensor (OFF)
Stops
EEV1: 300 pls
EEV2: 480 pls
100 - 500 pls
Close
All compressor operaiotn Stop
Keeps the operation mode
Stops
0 pls
0 pls
Open
Preparation process On Defrost operatiom Finishing processActuator
Slave 1 Slave 2
Compressor in operation
Compressor in operation
Stopped compressor
Master
Slave 1 Slave 2Master
Slave 1 Slave 2Master
INV INV INV
INV INV INV
INV INV INV
Compressor operate by
the lowest speed (20rps)
Outdoor units which satisfied the defrosting end judgment temperature
are operated at the lowest speed (20rps) for inverter compressor.
When the defrosting of all outdoor units ends, all outdoor unit stop.
The start rotation execution is done, and restarts.
Defrosting Defrosting
DefrostingDefrost end
Defrost end Defrost end Defrost end
Defrost end
Defrosting
All compressors operates and it defrosting.