6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Model: AOYG09KATA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 15
Height difference H (m)
Indoor unit is higher than outdoor
unit *
1
15 — — — 0.903
10 — — 0.964 0.918
7.5 — 0.988 0.968 0.922
5 0.992 0.992 0.972 0.925
0 1.000 1.000 0.980 0.933
Indoor unit is lower than outdoor
unit *
2
-5 1.000 1.000 0.980 0.933
-7.5 — 1.000 0.980 0.933
-10 — — 0.980 0.933
-15 — — — 0.933
HEATING
Pipe length (m)
5 7.5 10 15
Height difference H (m)
Indoor unit is higher than outdoor
unit *
1
15 — — — 0.943
10 — — 1.010 0.943
7.5 — 1.000 1.010 0.943
5 1.000 1.000 1.010 0.943
0 1.000 1.000 1.010 0.943
Indoor unit is lower than outdoor
unit *
2
-5 0.995 0.995 1.005 0.939
-7.5 — 0.993 1.002 0.936
-10 — — 0.999 0.934
-15 — — — 0.925
- 65 -
6-1. Model: AOYG09KATA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOYG09-22KATA
OUTDOOR UNIT
AOYG09-22KATA