Power Cabling
Copyright Fujitsu Technology Solutions, Release August 2011
Hardware Installation ETERNUS DX80 S2 and DX90 S2
For FTS (CEMEA&I) only
Connect the rack PDUs
(Power Distribution Units) to
independent AC power phases
Make sure that the AC
power switches on each
Enclosure are turned off before
connecting their power cables
Connect each Power Supply
of an Enclosure to different
Power Distribution Units
PSU#0 inlet
PSU#1 inlet
PSU#0
inlet
PSU#1
inlet
Left
Rack PDU
Right
Rack PDU
Always follow the local
power cabling regulations!