7. Safety devices
Type of protection Protection form
Model
ARXG36KHTAP
ARXG45KHTAP
ARXG54KHTAP
Circuit protection Current fuse (PCB*) 250 V, 10 A
Fan motor protection
Thermal protection
program
Activate
100 ±5 °C
Fan motor stop
Reset
70 ±15 °C
Fan motor restart
Current protection 7.58 A
*: Printed Circuit Board