6-2. Models: AOHG45KRTA and AOHG54KRTA
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length (m)
5 7.5 10 20 30 40 50
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.900 0.879 0.858
20 0.937 0.915 0.894 0.872
10 0.973 0.952 0.931 0.908 0.887
7.5 0.988 0.977 0.956 0.934 0.913 0.891
5 0.992 0.992 0.981 0.960 0.938 0.916 0.894
0 1.000 1.000 0.989 0.967 0.945 0.923 0.901
Indoor unit is lower than
outdoor unit *2
-5 1.000 1.000 0.989 0.967 0.945 0.923 0.901
-7.5 1.000 0.989 0.967 0.945 0.923 0.901
-10 0.989 0.967 0.945 0.923 0.901
-20 0.967 0.945 0.923 0.901
-30 0.945 0.923 0.901
HEATING
Pipe length (m)
5 7.5 10 20 30 40 50
Height difference H (m)
Indoor unit is higher
than outdoor unit *1
30 0.978 0.968 0.958
20 0.988 0.978 0.968 0.958
10 0.998 0.988 0.978 0.968 0.958
7.5 1.000 0.998 0.988 0.978 0.968 0.958
5 1.000 1.000 0.998 0.988 0.978 0.968 0.958
0 1.000 1.000 0.998 0.988 0.978 0.968 0.958
Indoor unit is lower than
outdoor unit *2
-5 0.995 0.995 0.993 0.983 0.973 0.963 0.953
-7.5 0.993 0.991 0.981 0.971 0.961 0.951
-10 0.988 0.978 0.968 0.958 0.948
-20 0.968 0.958 0.949 0.939
-30 0.949 0.939 0.929
- 54 -
6-2. Models: AOHG45KRTA and AOHG54KRTA 6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOHG36-54KRTA
OUTDOOR UNIT
AOHG36-54KRTA

Table of Contents

Related product manuals