2) Static pressure
Select the appropriate static pressure according to the installation conditions.
Function number Setting value Setting description Factory setting
03 30 Pa
04 40 Pa
05 50 Pa
06 60 Pa
07 70 Pa
08 80 Pa
09 90 Pa
10 100 Pa
11 110 Pa
12 120 Pa
13 130 Pa
26 14 140 Pa
15 150 Pa
16 160 Pa
17 170 Pa
18 180 Pa
19 190 Pa
20 200 Pa
31
Standard
(47 Pa: 36 type; 60 Pa: 45, 54 type)
32 Automatic airflow adjustment
NOTE: Range of static pressure is different by model.
If the static pressure is set above maximum range, the setting will be the same as the maxi-
mum.
Example:
For 45, 54 type models, setting "170 Pa" (17) to "200 Pa" (20) will be the same as "160 Pa"
(16).
Type name Setting of static pressure range
36 type 30 to 200 Pa
45 and 54 type 30 to 160 Pa
For details, refer to Chapter 5-1. "Fan performance curve" on page 10.
- 34 -
9-2. Function settings by using remote controller 9. Function settings