¢ Cool air prevention control (heating mode)
The maximum value of the indoor fan speed is set as shown below, based on the detected tempera-
ture by the indoor heat exchanger sensor on heating mode.
• Normal operation
Indoor heat exchanger
temperature rises
27°C
Stop
Setting fan mode
13 minutes later:
Indoor heat exchanger
temperature rises
27°C
LOW
Setting fan mode
• 10 °C HEAT operation
Indoor heat exchanger
temperature rises
27°C
LOW
AUTO
¢ Moisture return prevention control (cooling and dry mode)
Switch the airflow AUTO at cooling mode, and the indoor fan motor will run as shown below.
Compressor
On
Off
Indoor fan
setting airflow
LOW
Off
5 60 360 120 360 60 5 (sec)
3-1. Indoor fan control - (04-9) - 3. Fan control