4-2. Inverter compressor
Check point 1. Check connection
Check terminal connection of compressor (loose or incorrect wiring)
R(U)
(RED)
S(V)
(WHITE)
T(W)
(BLACK)
Main PCB
Check terminal connection of main PCB (loose or incorrect wiring)
Main PCB
P402(W)
Compressor
BLACK
WHITE
RED
P400(U)
P401(V)
Check point 2. Check winding resistance
Check winding resistance of each terminal.
Resistance value: 1.546 Ω ±8 % at 20 °C
R(U)
T(W)
S(V)
RED
WHITE
BLACK
→ If the resistance value is 0 Ω or infinite, replace compressor.
Check point 3. Replace inverter PCB
If check point 1 to 2 do not improve the symptom, replace main PCB.