Available Sensor ID
Sensor ID Item Unit Remarks
00 140 Operation or Stop (External input) 00: —
0: Off, 1: On
—: When the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 141 Emergency stop (External input) 00: —
0: Off, 1: On
—: When the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 142 Forced stop (External input) 00: —
0: Off, 1: On
—: When the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 143 Operation or Stop 2 (External input) 00: —
0: Off, 1: On
—: When the function setting 46 is
not set
NOTE: Available only for external
input port of the indoor unit
00 144
External thermostat off (External
input)
00: — 0: Off, 1: On
00 145 Cooling operation on (External input) 00: — 0: Off, 1: On
00 146
Cooling operation off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 155
Operation or Stop On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 156 Error On/Off (External output) 00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 157
Indoor unit fan interlocking On/Off
(External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 158
Cooling thermostat On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 159
Requested cooling strength On/Off
(External output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 160
External heater On/Off (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
00 161
Heating operation status (External
output)
00: —
0: Off, 1: On
NOTE: The value is output even if
the function setting or
rotary switch is not set.
6-13. Unit status monitoring and the detected value indication
- (04-25) - 6. Various control