1-5. Compressor frequency limitation by outdoor temperature
The minimum rotation number of compressor is limited by outdoor temperature as below.
Cooling/Dry mode
F zone
38°C
E zone
19°C
D zone
10°C
C zone
B zone
A zone
0°C
-10°C
Model name Outdoor temperature zone
Limitation of compressor
frequency
AOHG18KMTA
A zone 26 rps
B zone 26 rps
C zone 26 rps
D zone 16 rps
E zone 12 rps
F zone 18 rps
AOHG24KMTA
A zone 24 rps
B zone 24 rps
C zone 24 rps
D zone 14 rps
E zone 14 rps
F zone 22 rps
1-5. Compressor frequency limitation by outdoor temperature - (04-5) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS