2-26. E: 86. High pressure switch error (Outdoor unit)
Indicator Indoor unit
Operation indicator 8 time flash
Timer indicator 6 time flash
Economy indicator Continuous flash
Error code E: 86
Detective actuator
Outdoor unit main PCB
→hen pressure switch open is detected in 10 seconds
after the power is turned on.
High pressure switch
Forecast of cause
High pressure switch connector disconnection or open
High pressure switch characteristics failure
Main PCB failure
Check point 1. Check the high pressure switch connection state
Check connector and wiring connection state.
Check if cable is open
-> Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Check the high pressure switch characteristics
Check switch characteristics.
For the characteristics of the high pressure switch, refer to below.
Check point 3. Replace main PCB
Change main PCB and check operation again.
End
Type of contact
C
H
Pressure
Characteristics of pressure switch
Pressure switch 1
Contact: Short  Open 4.2—4.05 MPa
Contact: Open  Short 3.2±0.15 MPa
24 model: P20
2-26. E: 86. High pressure switch error (Outdoor unit) - (03-31) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING