8-3. Current release control
The rotation number of compressor is controlled so that the outdoor unit input current does not ex-
ceeds current limit value set according to the outdoor temperature.
The rotation number of compressor returns according to the operation mode, when the current be-
comes lower than the release value.
¢ Model: AOHG18KMTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
50°C ≤ Ta 4.5 A 4.0 A
46°C ≤ Ta < 50°C 4.5 A 4.0 A
40°C ≤ Ta < 46°C 6.0 A 5.5 A
12°C ≤ Ta < 40°C 9.0 A 8.5 A
2°C ≤ Ta < 12°C 9.0 A 8.5 A
Ta < 2°C 9.0 A 8.5 A
Heating
17°C ≤ Ta 7.0 A 6.5 A
12°C ≤ Ta < 17°C 9.0 A 8.5 A
5°C ≤ Ta < 12°C 11.0 A 10.5 A
Ta < 5°C 13.0 A 12.5 A
¢ Model: AOHG24KMTA
Operation mode Outdoor temp. (Ta) Trigger condition Release condition
Cooling
50°C ≤ Ta 7.0 A 6.5 A
46°C ≤ Ta < 50°C 7.0 A 6.5 A
40°C ≤ Ta < 46°C 9.5 A 9.0 A
12°C ≤ Ta < 40°C 12.5 A 12.0 A
2°C ≤ Ta < 12°C 12.5 A 12.0 A
Ta < 2°C 12.5 A 12.0 A
Heating
17°C ≤ Ta 10.5 A 10.0 A
12°C ≤ Ta < 17°C 13.0 A 12.5 A
5°C ≤ Ta < 12°C 14.5 A 14.0 A
Ta < 5°C 15.5 A 15.0 A
8-4. Cooling pressure over-rise protection
→hen the outdoor unit heat exchanger temperature reaches trigger condition below, the compressor
is stopped and trouble display is performed.
Trigger condition 65°C
8-5. Compressor temperature protection
→hen the compressor temperature sensor detects higher than the trigger condition below, the com-
pressor is stopped. →hen the compressor temperature sensor detects the release condition, the pro-
tection is released.
Trigger condition 108°C
Release condition
80°C
(3 minutes after compressor stop)