Instruction manual 1353-EN” 13
Heat pump, split, single service
Holidaysprogramme,circuit1
641 Preselection Period1to8 Period1
642 Dateholidaysstart(Day/Month) 01.01…31.12 1
643 Dateholidaysend(Day/Month) 01.01…31.12 1
648 Heatingscheduleduringtheholidays
Frostprotection,Reduced
F r o s t
protection
Holidaysprogramme,circuit2
Iftheinstallationconsistsof2heatingcircuits(onlywiththe2ndcircuitkitoption)
651 Preselection Period1to8 Period1
652 Dateholidaysstart(Day/Month) 01.01…31.12 1
653 Dateholidaysend(Day/Month) 01.01…31.12 1
658 Heatingscheduleduringtheholidays
Frostprotection,Reduced
F r o s t
protection
Heatingadjustment,circuit1
710 Comfortambienttemperaturesetpoint fromreduced
temperatureto35°C
0,5°C 20°C
712 Reducedambienttemperaturesetpoint
fromfrost-freetemp…to
comforttemperature
0,5°C 18°C
714 Frost-freeambienttemperaturesetpoint from4°C…
toreducedtemperature
0,5°C 8°C
Coolingadjustmentcircuit1
Iftheinstallationisfittedwiththecoolingkit(onlywiththecoolingkitoption)
901 Operatingmode Off, Automatic Off
902 Comfortambienttemperaturesetpoint 17...40°C 0,5°C 24°C
907 Release 24h/day, Time
programmeHC, Time
programme5/Refresh
24h/day
If the installation is fitted with a DHW tank, set the parameter 907 to "Time programme 5 / Cooling" (in order to
activatecoolingonlyduringthedayandleavetheDHWsystemtooperateduringthenight).
Heatingadjustment,Circuit2
Iftheinstallationconsistsof2heatingcircuits(onlywiththe2ndcircuitkitoption)
1010 Comfortambienttemperaturesetpoint fromreduced
temperatureto35°C
0,5°C 20°C
1012 Reducedambienttemperaturesetpoint fromfrost-freetemp…to
comforttemperature
0,5°C 18°C
1014 Frost-freeambienttemperaturesetpoint from4°C…toreduced
temperature
0,5°C 8°C
DHWsetting(domestichotwater)(onlywiththeDHWkitoption)
1610 Comfortsetting
reducedsetting(line1612)…
to65°C
1 60°C
Thebackupelectricalsystemisrequiredtoreachthislevel.
1612 Reducedsetting
8°C...to
comfortsetting(line1610)
1 40°C
Line
Function Settingrange
ordisplay
Setting
increment
B a s i c