Con guring room thermostat
(wireless)(option)
To con gure the room thermostat and connect it to the
appropriate heating zone:
- Hold down the presence key for more than 3 seconds.
The room thermostat displays RU and a number
ashes.
- Turn the wheel to choose the zone (1, 2).
If the installation is tted with 2 room thermostats,
- First connect one room thermostat and con gure
it in zone 2,
- Then connect the other room thermostat and
con gure it as default in zone 1.
- Hold down the presence key; the room
thermostat displays "P1" and a ashing number.
1: Automatic recording: a correction of the setting
with the button is adopted without any particular
con rmation (timeout) or by pressing the mode key.
2: Recording with con rmation: a correction of the
setting with the button is not adopted until the mode
key is pressed.
- Press the presence key again; the room thermostat
displays "P2" and a ashing number.
0: OFF: all the operating elements are engaged.
1: ON: the following operating elements are locked:
- Switching over the heating circuit's operating
mode,
- Adjusting the comfort setting,
- Changing the operating level.
The room thermostat displays OFF for 3 seconds when
a locked button is pressed.
Con guring room control unit
(wireless) (option)
During commissioning, after an initialisation period of
approx. 3 minutes, the user’s language must be set:
- Press
OK
.
- Choose menu "Operator section".
- Choose language.
- Select the language (English, Deutsch, Français,
Italiano, Nederlands, Español, Português, Dansk…).
In the case of 2 heating circuits,
- Choose the allocation of the room control unit
(room appliance 1 or 2…) line 40* (see page 49).
- According to the allocation selected check and, if
necessary, modify the settings for lines 42*, 44*, 48*
(see page 49).
Line Function
Setting range
or display
Setting
increment
Basic
setting
40 I Use as... Room appliance 1, 2, P,
User interface 1, 2, P,
Service appliance
Room
appliance 1
This line regulates the use of the room control unit. Depending on how it is used, other settings will be necessary
(lines 42, 44, 48).
42 I Appliance allocation 1 Heating circuit 1,
Heating circuit 1 & 2,
Heating circuit 1 & P,
All the heating circuits
Heating
circuit 1
44 I Operation HC2 (command HC2) Commonly with HC1,
Independent
Commonly
with HC1
This function enables you to choose whether you wish the room thermostat (as an option) to act on both zones or just
a single zone.
48 I Occupancy control switch function Without,
Heating circuit 1,
Heating circuit 2,
Common
* These parameter lines are only accessible from the room control unit.