EasyManuals Logo

Fujitsu WOYA080LFCA Design & Technical Manual

Fujitsu WOYA080LFCA
213 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
- (OU01 - 29) -
Outdoor unit / Single phase
OUTDOOR UNIT
WO
A060-100LF
OUTDOOR UNIT
WO
A060-100LF
SAFETY DEVICES9.
Protection from
Model
WO
A060LFCA
WO
A080LFCA
WO
A100LFTA
Circuit protection
Current fuse
(Near the terminal)
250V 20A 250V 25A 250V 25A
Current fuse
(Main PCB)
250V 15A
250V 3.15A 250V 3.15A250V 10A
250V 3.15A
Fan motor protection
Thermal protection
program
Activate (at 100 ± 10
°C)
: Fan motor stop
Reset (at 95 ± 10
°C)
: Fan motor restart
Activate (at 150 ± 15
°C)
:
Fan motor stop
Reset (at 120 ± 15
°C)
:
Fan motor restart
Compressor protection
Thermal protection program
(Compressor temp.)
Activate (at 108
°C)
: Compressor stop
Reset (at 80
°C)
: Compressor restart
Thermal protection program
(Discharge temp.)
Activate (at 110
°C)
: Compressor stop
Reset (after 7 minutes
)
: Compressor restart
High pressure protection
Thermal protection program
(Heat exchanger temp.)
Activate (at 67
°C)
: Compressor stop
Reset (at 63
°C)
: Compressor restart
Pressure sensor
Activate (at 4.2 MPa
)
: Compressor stop
Reset (at 3.0 MPa
)
: Compressor restart
Low pressure protection
(Cooling mode only)
Pressure sensor
Activate (at 0.12 MPa
)
: Compressor stop
Reset (at 0.15 MPa
)
: Compressor restart

Table of Contents

Other manuals for Fujitsu WOYA080LFCA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu WOYA080LFCA and is the answer not in the manual?

Fujitsu WOYA080LFCA Specifications

General IconGeneral
BrandFujitsu
ModelWOYA080LFCA
CategoryHeat Pump
LanguageEnglish

Related product manuals