- (OU01 - 05) -
Outdoor unit / Single phase
OUTDOOR UNIT
WO
G112-140LCTA
OUTDOOR UNIT
WO
G112-140LCTA
TECHNICAL SPECIFICATIONS2-2.
Model name (Outdoor unit) WO
Û
G112LCTA WO
Û
G140LCTA
Enclosure
Colour BEIGE (10YR 7.5/1.0)
Material Steel sheet
Dimensions
(H x W x D)
Net
mm
1290 x 900 x 330
Gross 1430 x 1050 x 445
Weight
Net
kg
92
Gross 100
Heat exchanger type
Dimensions (H x W x D)
mm
1260 x 900 x 36.4
Fin pitch 1.3
Rows & Stages 2 x 60
Pipe type Copper
Fin
Type (Material) Corrugate (Aluminium)
Surface treatment Corrosion resistance (Blue n)
Fan
Airow rate Heating m³/h 6,200
Type x Q'ty Propeller x 2
Discharge direction Horizontal
Motor Quantity 2
Motor output W 100
Compressor
Type x Q'ty DC 2 rotary (Liquid injection) x 1
Motor output W 3,750
Operation range
Heating
Min °CDB -25
Max °CWB 35
Sanitary
water
Min °CDB -25
Max °CWB 35
Refrigerant
Type R410A
Charge g 2,500
Control Expansion valve (electric type)
Nr of circuits 1
Refrigerant oil
Type VG74
Charged volume l 1.55
Connection pipe
Type
Liquid Flare connection
Gas Flare connection
Size
(Standard)
Liquid
mm
9.52
Gas 15.88
Drain
Type x Q'ty Socket x 3
Size mm 20
Pre-charge length
m
15
Max. length 20
Min. length 5
Additional refrigerant charge g/m 50
Max. height difference m 15
Defrost method Reverse cycle
Defrost control Outdoor heat exchanger temperature sensor
Capacity control method Inverter control