- (OU01 - 28) -
Outdoor unit / 3 phase
OUTDOOR UNIT
WO
K112-160LCTA
OUTDOOR UNIT
WO
K112-160LCTA
SAFETY DEVICES9.
Protection from
Model
WO
Û
K112LCTA WO
Û
K140LCTA WO
Û
K160LCTA
Circuit protection Current fuse (Main PCB)
5A 250V
3.15A 250V
10A 250V
Fan motor protection Thermal protecter
Activate
150±20ºC
Fan motor stop
Reset
120±20ºC
Fan motor restart
Compressor protection
Thermal protection program
(Compressor temp.)
Activate
112ºC
Compressor stop
Reset
80ºC
Compressor restart
Thermal protection program
(Discharge temp.)
Activate
115
°C
Compressor stop
Reset
after 7 minutes
Compressor restart
High pressure protection
Thermal protection program
(Heat exchanger temp.)
Activate
68
°C
Compressor stop
Reset
63
°C
Compressor restart
Pressure sensor
Activate
4.2 MPa
Compressor stop
Reset
3.0 MPa
Compressor restart
Low pressure protection
(Cooling mode only)
Pressure sensor
Activate
0.12 MPa
Compressor stop
Reset
0.15 MPa
Compressor restart

Table of Contents

Other manuals for Fujitsu WOYA080LFCA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu WOYA080LFCA and is the answer not in the manual?

Fujitsu WOYA080LFCA Specifications

General IconGeneral
BrandFujitsu
ModelWOYA080LFCA
CategoryHeat Pump
LanguageEnglish

Related product manuals