INSTALLATION EDR-SOLA-IOM-2022-0216 SECTION 2
2-44
3. Heat conductive compound, also known as thermal
paste, is applied during installation between the
probe and thermowell to ensure accurate temperature
readings.
4. Mount the Aquastat in a location that is accessible for
operation and maintenance. Take care to not pinch or
otherwise damage the capillary tube.
5. Remove the 72-73 jumper, and wire the Aquastat to the
associated terminal blocks.
` BOILER STATUS CONTACT
A dry contact is provided for remote monitoring of boiler
status. When the main gas valve is enabled, the contact is
closed. This requires a 120 VAC relay (P/N 2-45-880360), rated
for 5 Amps maximum.