General Operation of the Boiler
Excessive cycling will reduce the useful life of any piece of mechanical
equipment. Endura boilers should be operated and controlled so the boiler
cycles less than 12,000 times per year. Endura boilers should be operated and
controlled so that the temperature dierential across the boiler does not exceed
100°F (38°C).