© Fulton Group N.A., Inc. 2022
3-34
OPERATION EDR-SOLA-IOM-2022-0216 SECTION 3
! WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.
Non-Fulton product information is for
reference purposes only. No Fulton
document may substitute for full
review of documentation available
from the component manufacturer.
General Operation of the Boiler
Excessive cycling will reduce the useful life of any piece of mechanical
equipment. Endura boilers should be operated and controlled so the boiler
cycles less than 12,000 times per year. Endura boilers should be operated and
controlled so that the temperature dierential across the boiler does not exceed
100°F (38°C).