2.3.9 – SLAM SHUT VALVE SPRING RANGE (SET-POINT)
SSV – ACTUADOR H
SPRING COLOR PART NUMBER RANGE
PURPLE 01.52.61 0.3 – 1.5 bar
RED 01.52.62 1.0 – 5.0 bar
YELLOW 01.51.54 4.0 – 11.0 bar
SSV – ACTUATOR PH
SPRING COLOR PART NUMBER RANGE
BROWN 01.52.64 10.0 – 16.0 bar
ZINCATED 01.52.25 14.0 – 38.0 bar
WHITE 01.52.36 28.0 – 60.0 bar
2.3.10 – ACCURACY AND LOCK UP
Pressure regulator: AC up to 2,5% / SG up to 5%