General
6
2.4 PACKAGING LABEL
2.5 WARNING LABEL
WARNINGS !
.Read the technical instructions before installing
the boiler.
.Installation and comissioning must be done by
authorized qualified technicians.
.The boiler may only be installed in a room which
complies with the appropriate ventilation require-
2.6 DATA LABEL
Wall Hung Gas Condensing Boilers
Model : Wallcon
Efficiency Level :
Standards :
Flue (appliance) Types : B23, C13, C33,
C43, C53, C63, C83
Production Year :
IP
Istanbul Endustri ve Ticaret Serbest Bolgesi
Parsel 110
34957 , Tuzla, Istanbul,
www.gassero.com
ATTENTION : The boiler is
Pressure of G20 - 21 mbar .
Pressure
Gas
Category
Gas
Destination
Countries of
NO Class : 5
Power Consumption :
Max. Working Temperature :
o
85 C
Max. Working Pressure(PMS) : bar
o
C)
o
C)
.Read the user instructions before operating the
boiler.
ments and which is seperated from living rooms.
The Wallcon condensing boilers must be installed in rooms
used exclusively for this purpose, provided with adequately
sized ventilation openings, in compliance with any current
standards and low applicable. If the combustion air is taken
from outside the room where the boiler is installed,
Wallcon boilers operates as a room-sealed appliance (type C).
Provide enough clearance to access the safety and
control devices and to carry out the servicing operations.
Check that the index of protection of the boiler is
suitable for the characteristics of the room where
the appliance is installed.
If the boilers operate on gas fuel with a higher specific
weight than air, the electrical parts must be located at
least 500 mm from the floor.
The boilers cannot be installed outside as they are
not designed for outdoor operation.
When installing and operating the boilers it is necessary to
keep a safe 200 mm distance from combustible materials
with combustibility degrees B,C1,C2 .
For easily flammable materials with combustibility degree C3
which burn quickly and by themselves also after the ignition
source removal the safe distance is doubled it means 400 mm.
0051 -14
1 2 3 4 5 6 7 8 9 0 1 2 3
Product Model :
Serial Number :
1 2 3 4 5 6 7 8 9 0 1 2 3
Heat Output :
Gas Type : 2H G20-21 mbar-N.Gas
Countries of
Destination
1 2 3 4 5 6 7 8 9 0 1 2 3
Product Code :
Serial Number :
Product Code :
1 2 3 4 5 6 7 8 9 0 1 2 3
MASTER
SLAVE
Pn Max. (kW) :
Pn Min. (kW) :
Pn Max. (kW) :
Pn Min. (kW) :
MASTER
SLAVE