GASSONIC OBSERVER-i
76
Address
(hex)
Parameter Function Data Type Data range Access
3B Structure time
Low
Hi byte – min, low
byte – sec for
warning event log
entries
Numeric value 0 – 65535
Warn
3C Reserved Reserved Numeric value 0
3D Reserved Reserved Numeric value 0
3E Warn Event
Count
Warning Event
Count
Numeric value 0 – 65535
Warn
3F Alarm Seconds
Time Hi
Seconds Time Hi
for alarm event log
entries
Numeric value 0 – 65535
Alarm
40 Seconds Time
Low
Seconds Time Low
for alarm event log
entries
Numeric value 0 – 65535
Alarm
41 Structure time Hi Hi byte – year, low
byte – month for
alarm event log
entries
Numeric value 0 – 65535
Alarm
42 Structure time
Mid
Hi byte – day, low
byte – hour alarm
event log entries
Numeric value 0 – 65535
Alarm
43 Structure time
Low
Hi byte – min, low
byte – sec for alarm
event log entries
Numeric value 0 – 65535
Alarm
44 Alarm Detection
Type and Peak
dB
Alarm Detection
Type and Peak dB
Numeric value 0-65535
Alarm
45 Reserved Reserved Numeric value 0
46 Alarm Event
Count
Alarm Event Count Numeric value 0 – 65535
Alarm
47 Fault
Seconds time Hi
Seconds Time Hi
for fault event log
entries
Numeric value 0 – 65535
Fault
48 Seconds time
Low
Seconds Time Low
for fault event log
entries
Numeric value 0 – 65535
Fault
49 Structure time Hi Hi byte – year, low
byte – month for
fault event log
entries
Numeric value 0 – 65535
Fault