LOCATION 65 - KEYPAD PANIC COMMUNICATOR CODE, SLOW SPEED FORMATS ONLY (2 segments,
numerical data)
Location 65 contains the tens and ones digits that will be sent for a 4+2 format if the keypad "Panic" is enabled in the
partition feature selection Segment 1 contains the tens digit segment 2 contains the ones digit.
LOCATION 66 - KEYPAD MULTIPLE CODE ENTRY TAMPER COMMUNICATOR CODE, SLOW SPEED
FORMATS ONLY (2 segments, numerical data)
Location 66 contains the tens and ones digits that will be sent for a 4+2 format if the keypad "Multiple Code Entry"
(Tamper) is enabled in the partition feature selection. Segment 1 contains the tens digit, segment 2 contains the ones
digit.
LOCATION 67 - BOX TAMPER / BOX TAMPER RESTORE COMMUNICATOR CODE, SLOW SPEED FORMATS
ONLY (4 segments, numerical data)
Location 67 contains the tens and ones digits that will be sent for a 4+2 format if the "Box Tamper" feature is enabled
in location 37. Segment 1 contains the tens digit of the "Box Tamper". Segment 2 contains the ones digit of the "Box
Tamper". Segment 3 contains the tens digit of the "Box Tamper Restore". Segment 4 contains the ones digit of the
"Box Tamper Restore".
LOCATION 68 - AC FAIL / AC FAIL RESTORE COMMUNICATOR CODES, SLOW SPEED FORMATS ONLY
(4 segments, numerical data)
Location 68 contains the tens and ones digits for a 4+2 format that will be sent if "AC Fail Reporting" is enabled.
Segment 1 contains the tens digit of the "AC Fail Reporting". Segment 2 contains the ones digit of the "AC Fail
Reporting". Segment 3 contains the tens digit of the "AC Fail Restore". Segment 4 contains the ones digit of the "AC
Fail Restore".
LOCATION 69 - LOW BATTERY / LOW BATTERY RESTORE COMMUNICATOR CODES , SLOW SPEED
FORMATS ONLY (4 segments, numerical data)
Location 69 contains the tens and ones digits for a 4+2 format that will be sent if "Low Battery Reporting" is enabled..
Segment 1 contains the tens digit of the "Low Battery Reporting". Segment 2 contains the ones digit of the "Low
Battery Reporting". Segment 3 contains the tens digit of the "Low Battery Restore". Segment 4 contains the ones
digit of the "Low Battery Restore".
LOCATION 70 - AUX POWER OVERCURRENT/ AUX POWER OVERCURRENT RESTORE COMMUNICATOR
CODES, SLOW SPEED FORMATS ONLY (4 segments, numerical data)
Location 70 contains the tens and ones digits for a 4+2 format that will be sent if "Aux Power Overcurrent Reporting"
is enabled. Segment 1 contains the tens digit of the "Aux Power Overcurrent ReportIng". Segment 2 contains the
ones digit of the "Aux Power Overcurrent Reporting". Segment 3 contains the tens digit of the "Aux Power Overcurrent
Restore". Segment 4 contains the ones digit of the "Aux Power Overcurrent Restore".
LOCATION 71 - BELL TAMPER AND BELL TAMPER RESTORE COMMUNICATOR CODES, SLOW SPEED
FORMATS ONLY (4 segments, numerical data)
Location 71 contains the tens and ones digits for a 4+2 format that will be sent if siren supervision reporting is
enabled. Segment 1 contains the tens digit of the "Bell Tamper Reporting". Segment 2 contains the ones digit of the
"Bell Tamper Reporting". Segment 3 contains the tens digit of the "Bell Tamper Restore". Segment 4 contains the
ones digit of the "Bell Tamper Restore".
LOCATION 72 - TELEPHONE LINE CUT AND TELEPHONE LINE CUT RESTORE COMMUNICATOR CODES,
SLOW SPEED FORMATS ONLY (4 segments, numerical data)
Location 72 contains the tens and ones digits for a 4+2 format that will be sent if "Telephone Line Cut Reporting" is
enabled. Segment 1 contains the tens digit of the "Telephone Line Cut Reporting". Segment 2 contains the ones digit
of the "Telephone Line Cut Reporting". Segment 3 contains the tens digit of the "Telephone Line Cut Restore".
Segment 4 contains the ones digit of the "Telephone Line Cut Restore".
LOCATION 73 - GROUND FAULT AND GROUND FAULT RESTORE COMMUNICATOR CODES, SLOW SPEED
FORMATS ONLY (4 segments, numerical data)
Location 73 contains the tens and ones digits for a 4+2 format that will be sent if "Ground Fault Reporting" is enabled,
and the NX-870 is installed. Segment 1 contains the tens digit of the "Ground Fault Reporting". Segment 2 contains
the ones digit of the "Ground Fault Reporting". Segment 3 contains the tens digit of the "Ground Fault Restore".
Segment 4 contains the ones digit of the "Ground Fault Restore".

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Interlogix NX-8 - Security NetworX System and is the answer not in the manual?

GE Interlogix NX-8 - Security NetworX System Specifications

Power IconPower
operating power16.5 VAC 25, 40, or 50 VA Transformer
auxiliary power with 25 VA transformer12 VDC Regulated 500 mA
auxiliary power with 40 or 50 VA transformer12 VDC Regulated 1 AMP
auxiliary power with NX-320 power supply12 VDC Regulated 2 AMPS + Control
Loop Specifications IconLoop Specifications
standard loop resistance300 Ohms Maximum
2-wire smokes resistance30 Ohms Maximum
loop responseSelectable 50mS or 500mS
Operating Environment IconOperating Environment
operating temperature32 to 120 degrees F
built-in siren driver2-tone (Temporal and Yelp)
LED keypad current draw130 mA max.
Weight and Dimensions IconWeight and Dimensions
metal enclosure dimensions11.25" Wide x 11.25" High x 3.50" Deep
shipping weight9 lbs.
LED keypad dimensions6.4" Wide x 4.0" High x 1.1" Deep
NX-148 LCD keypad dimensions6.4" Wide x 5.3" High x 1.0" Deep