EasyManua.ls Logo

GE 760

GE 760
102 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 6: DNP POINT LISTS ANALOG INPUT / ANALOG INPUT CHANGE
750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE 6 - 7
45 165 F49 User Input D Class 1
46 166 F49 User Input E Class 1
47 167 F49 User Input F Class 1
48 168 F49 User Input G Class 1
49 169 F49 User Input H Class 1
50 170 F49
Negative Sequence Instantaneous
Overcurrent
Class 1
51 171 F49 Negative Sequence Time Overcurrent Class 1
52 172 F49 Negative Sequence Overvoltage Class 1
53 173 F49 Undervoltage Restoration Class 1
54 174 F49 Underfrequency Restoration Class 1
55 175 F49 Phase Time Overcurrent 2 Class 1
56 176 F49 Frequency Decay Class 1
57 177 F49 Negative Sequence Directional Is Reverse Class 1
58 178 F49 Sensitive Ground Instantaneous Overcurrent Class 1
59 179 F49 Sensitive Ground Time Overcurrent Class 1
60 180 F49 Sensitive Ground Directional Is Reverse Class 1
61 181 F1 Phase A RMS Current (see Note 3) Class 2
62 182 F1 Phase B RMS Current (see Note 3) Class 2
63 183 F1 Phase C RMS Current (see Note 3) Class 2
64 184 F1 Percent Of Load-To-Trip (see Note 3) Class 2
65 185 F1 Ground Current (see Note 3) Class 2
66 186 F3 Phase A-Neutral RMS Voltage (see Note 3) Class 2
67 187 F3 Phase B-Neutral RMS Voltage (see Note 3) Class 2
68 188 F3 Phase C-Neutral RMS Voltage (see Note 3) Class 2
69 189 F3 Phase A-Phase B RMS Voltage (see Note 3) Class 2
70 190 F3 Phase B-Phase C RMS Voltage (see Note 3) Class 2
71 191 F3 Phase C-Phase A RMS Voltage (see Note 3) Class 2
72 192 F3 Sensitive Ground Current (see Note 3) Class 2
Table 3: Analog Inputs DNP Points (Sheet 3 of 8)
Index when Point
Mapping is:
Format Description Event
Class
Assigned
Disable
d
Enabled