750/760 FEEDER MANAGEMENT RELAY – COMMUNICATIONS GUIDE 6 - 1
750/760 Feeder Management Relay
Chapter 6: DNP Point Lists
GE
Grid Solutions
DNP Point Lists
Binary Input / Binary Input Change
The point list for Binary Input (Object 01) and Binary Input Change (Object 02) is shown
below.
Table 1: Binary Inputs DNP Points
Index Description Event
Class
0 Relay In Service Class 1
1 Trip Condition(s) Active Class 1
2 Alarm Condition(s) Active Class 1
3 Protection Picked Up Class 1
4 Setpoint Group 1 Active Class 1
5 Setpoint Group 2 Active Class 1
6 Setpoint Group 3 Active Class 1
7 Setpoint Group 4 Active Class 1
8 Breaker Is Open Class 1
9 Breaker Is Closed Class 1
10
Reclosure Enabled
1
Class 1
11
Reclosure Disabled
1
Class 1
12
Reclosure In Progress
1
Class 1
13
Reclosure Locked Out
1
Class 1
14 Local Mode Active Class 1