16-
78
750/760 Feeder Management Relay GE Power Management
16.4 MODBUS MEMORY MAP 16 COMMUNICATIONS
16
3 Clear Diagnostic Data
F72 FORCE HARDWARE
0001h LED's (0=Normal, 1=Use LED force codes)
0002h
8
Reserved
0004h A100 Output Relay Watchdog (0=Normal, 1=Stop Updating)
0008h C400 Watchdog (0=Normal, 1=Stop Updating)
0010h 485 Communication Port (0=Normal, 1=Echo)
0020h E485 Communication Port (0=Normal, 1=Echo)
0040h A100 Watchdog (0=Normal, 1=Stop Updating)
F73 DYNAMIC OVERCURRENT PRIORITY
0 No Priority Adjustment
1 Voltage Restraint
2 Manual Close
3 Cold Load
4 Autoreclose
F74 DATA LOGGER SAMPLE RATE
0 1 cycle
1 1 second
2 1 minute
3 5 minutes
4 10 minutes
5 15 minutes
6 20 minutes
7 30 minutes
8 60 minutes
F75 UNITS OF LENGTH
0 km
1Miles
F76 TYPE OF FAULT
0001h øA (0=Not involved, 1= Involved)
0002h øB (0=Not involved, 1= Involved)
0004h øC (0=Not involved, 1= Involved)
0008h Ground (0=Not involved, 1= Involved)
Example: øB to øC to Ground = 000Eh
F77
2
ANALOG OUTPUT PARAMETER TYPE
0 Disabled
1 Phase A Current
Table 16–16: MODBUS MEMORY MAP DATA FORMATS (Sheet 19 of 24)
TYPE VALUE / BIT
MASK
DESCRIPTION
1 2 3 4 5 6 7 8 9
For explanation of Table footnotes, see page 16–83.