Modifications reserved Page 38/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc Operating Manual SitePro 10-15-20-30-40 kVA / S8
SP_010-300_S6_RPA-IM0048_02
P3
B
P13
P11
A
J62
J52
JA-1
JB-1
JP2
IM 0048
JP1
JP4
JP3
JP1
JP2 JP3
JP4
Fig. 5.9.2-2 Bus connection on terminal units
Terminal units
On the parallel bus PCB P34 – Bus Interface (IM0048), of the first and last units (terminal) of the
Parallel System the Jumpers JP1, JP2, JP3 and JP4 must be inserted
.
SP_010-300_S6_RPA-IM0048_03
P3
P13
P11
JA (2)
JB (2)
JP2
IM 0048
JP1
JP4
JP3
JA (1)
JB (1)
JP1
JP2
JP4
JP3
J62
BA
J52
Fig. 5.9.2-3 Bus connection on intermediate units
Intermediate units
On the parallel bus PCB P34 – Bus Interface (IM0048) of the intermediate units of the Parallel System
the Jumpers JP1, JP2, JP3 and JP4 must be removed
.
NOTE !
In a Parallel System composed of 2 or more units, only the first and last units (having
1 input JA and JB free) have the Jumper JP1, JP2, JP3 and JP4 inserted on parallel bus