CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 11-135
80598 0x9E95 Relays 0 0xFFFFFFFF 1 FC198 0 1
80600 0x9E97 Events 0 1 1 FC126 1 1
80601 0x9E98 Targets 0 2 1 FC101 1 1
Close Circuit 3 Monitoring
80606 0x9E9D Function 0 4 1 FC100A 0 1
80607 0x9E9E Pickup Delay 0 6000000 1 s F13 10000 1
80609 0x9EA0 Dropout Delay 0 6000000 1 s F13 0 1
80611 0x9EA2 Bypass Breaker State 0 1 1 FC126 0 1
80612 0x9EA3 Breaker Status Opened 0 0xFFFFFFFF 1 FC142 0 1
80614 0x9EA5 Block 0 0xFFFFFFFF 1 FC142 0 1
80616 0x9EA7 Relays 0 0xFFFFFFFF 1 FC198 0 1
80618 0x9EA9 Events 0 1 1 FC126 1 1
80619 0x9EAA Targets 0 2 1 FC101 1 1
Breaker 1 Arcing Current Config
80640 0x9EBF Function 0 4 1 FC100A 0 1
80642 0x9EC1 Initiation 0 0xFFFFFFFF 1 FC142 0 1
80644 0x9EC3 Delay 0 6000000 1 s F13 30 1
80646 0x9EC5 Alarm Level 0 50000 1 kA2-cyc F0 1000 1
80647 0x9EC6 Relays 0 0xFFFFFFFF 1 FC198 0 1
80649 0x9EC8 Block 0 0xFFFFFFFF 1 FC142 0 1
80651 0x9ECA Events 0 1 1 FC126 1 1
80652 0x9ECB Targets 0 2 1 FC101 1 1
Breaker 1 Health
80710 0x9F05 Function 0 4 1 FC100A 0 1
80711 0x9F06 Mode 0 1 1 FC277 0 1
80712 0x9F07 Preset Trip Counter 0 100000 1 F10 0 1
80714 0x9F09 Trip Trigger 0 0xFFFFFFFF 1 FC142 0 1
80716 0x9F0B Close Trigger 0 0xFFFFFFFF 1 FC142 0 1
80718 0x9F0D Open Status 0 0xFFFFFFFF 1 FC142 0 1
80720 0x9F0F Close Status 0 0xFFFFFFFF 1 FC142 0 1
80722 0x9F11 Spring Charge Status 0 0xFFFFFFFF 1 FC142 0 1
80724 0x9F13 Trip Time Pickup 0 6000000 1 s F13 50 1
80726 0x9F15 Close Time Pickup 0 6000000 1 s F13 50 1
80728 0x9F17 Incomplete Trp/Cls Time 0 6000000 1 s F13 100 1
80730 0x9F19 Arc Time Pickup 0 6000000 1 s F13 100 1
80732 0x9F1B Incomplete Arc Time 0 6000000 1 s F13 300 1
80734 0x9F1D Spring Charge Time
Pickup
0 6000000 1 s F13 15000 1
80736 0x9F1F Incomplete Charge Time 0 6000000 1 s F13 45000 1
80738 0x9F21 Arc Energy Pickup 1 100000 1 kA2-cyc F10 1000 1
80740 0x9F23 Alarm Counter 1 100 1 F0 5 1
80741 0x9F24 Relays 0 0xFFFFFFFF 1 FC198 0 1
80743 0x9F26 Block 0 0xFFFFFFFF 1 FC142 0 1
80745 0x9F28 Events 0 1 1 FC126 1 1
80746 0x9F29 Targets 0 2 1 FC101 1 1
Broken Rotor Bar
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words