869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 8-1
869 Motor Protection System
Chapter 8: IEC 61850
GE
Digital Energy
IEC 61850
The optional communications processor supports both the IEC61850 GOOSE and IEC
61850 MMS Server service as per IEC 61850 standard Ed. 2. The GOOSE messaging service
provides the 869
unit the ability to Publish/Subscribe Digital Input Status and its Quality
and Timestamp to/from other IEDs with supporting GOOSE messaging service, while the
server support allows remote control center, RTU/Gateway, local HMI or other client role
devices access to the relay for monitoring and control. The configuration of IEC61850
services is accomplished using the 869
configuration software, EnerVista 8 Series
Setup
software. A rebooting MUST be done before any changes made take affect.
General
IEC61850 SERVER
The IEC 61850 Server (i.e., 869 relay) reports data to the IEC 61850 Client, such as Local
HMI, RTU and Gateway with the information of logical device, data sets, data control block,
logical nodes and their data attributes.
The following tables list the logical nodes and number of instances for each of the LNs that
are supported within the 869
relay.
LOGICAL NODES
Table 8-1: Communication Elements in the 869
869 Communications Elements Corresponding IEC61850
Logical node and number
of instances
Supported in 869
Port status LCCH (3)
Remote Device LGOS (8) Yes
Time master supervision LT MS
Time management LTIM
PHYSICAL DEVICE INFORMATION LPHD Yes
Logical Node 0 LLN0 Yes