11-138 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP
81225 0xA108 Measurement Type 0 2 1 FC254 0 1
81226 0xA109 Thermal 90% Response
Time
041 FC25521
81227 0xA10A Time Interval 0 4 1 FC255 3 1
81228 0xA10B Pickup 1 3000000 1 kvar F11 10000 1
81230 0xA10D Relays 0 0xFFFFFFFF 1 FC198 0 1
81232 0xA10F Block 0 0xFFFFFFFF 1 FC142 0 1
81234 0xA111 Events 0 1 1 FC126 1 1
81235 0xA112 Targets 0 2 1 FC101 1 1
Apparent Power Demand
81260 0xA12B Name 0 65535 1 F60_26 ApprntPwr
Dmd
26
81273 0xA138 Function 0 4 1 FC100A 0 1
81275 0xA13A Measurement Type 0 2 1 FC254 0 1
81276 0xA13B Thermal 90% Response
Time
041 FC25521
81277 0xA13C Time Interval 0 4 1 FC255 3 1
81278 0xA13D Pickup 1 3000000 1 kVA F11 10000 1
81280 0xA13F Relays 0 0xFFFFFFFF 1 FC198 0 1
81282 0xA141 Block 0 0xFFFFFFFF 1 FC142 0 1
81284 0xA143 Events 0 1 1 FC126 1 1
81285 0xA144 Targets 0 2 1 FC101 1 1
Pulse Output
81310 0xA15D Function 0 1 1 FC126 0 1
81311 0xA15E Pos Whs Pulse Increment 0 1000000 1 MWh F33 10000 1
81313 0xA160 Pos Whs Pulse Relays 0 0xFFFFFFFF 1 FC198A 0 1
81315 0xA162 Neg Whs Pulse Increment 0 1000000 1 MWh F33 10000 1
81317 0xA164 Neg Whs Pulse Relays 0 0xFFFFFFFF 1 FC198A 0 1
81319 0xA166 Pos VARhs Pulse
Increment
0 1000000 1 Mvarh F33 10000 1
81321 0xA168 Pos VARhs Pulse Relays 0 0xFFFFFFFF 1 FC198A 0 1
81323 0xA16A Neg VARhs Pulse
Increment
0 1000000 1 Mvarh F33 10000 1
81325 0xA16C Neg VARhs Pulse Relays 0 0xFFFFFFFF 1 FC198A 0 1
81327 0xA16E Events 0 1 1 FC126 1 1
81328 0xA16F Targets 0 2 1 FC101 1 1
Digital Counter 1
81360 0xA18F Function 0 1 1 FC126 0 1
81361 0xA190 Name 0 65535 1 F60_26 Counter 1 26
81374 0xA19D Units 0 65535 1 F60_6 units 6
81377 0xA1A0 Pre-set -2147483648 2147483647 1 F30 0 1
81379 0xA1A2 Compare -2147483648 2147483647 1 F30 0 1
81381 0xA1A4 Up 0 0xFFFFFFFF 1 FC142 0 1
81383 0xA1A6 Down 0 0xFFFFFFFF 1 FC142 0 1
81385 0xA1A8 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
81387 0xA1AA Reset 0 0xFFFFFFFF 1 FC142 0 1
81389 0xA1AC Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
81391 0xA1AE Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
Modbus
Address
Hex
Address
Description Min Max Step Units Format
Code
Factory
Default
Size in
Words