CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 11-297
382 Remote RTD 15 Alarm
383 Remote RTD 16 Alarm
384 Remote RTD 17 Alarm
385 Remote RTD 18 Alarm
FC151 unsigned 16 bits Element Status
This format shows the meaning of the Element Status values.
Refer to Format FC142 for exact information for each element.
There are cases where different meaning is given to each bit. PKP meaning "Open", for example.
0x0000 None Active
0x0001 Element PKP
0x0002 Element OP
0x0008 Phase A Pickup
0x0010 Phase B Pickup
0x0020 Phase C Pickup
0x0040 Phase A Operate
0x0080 Phase B Operate
0x0100 Phase C Operate
0x0200 Element Is Latched
0x0400 Configurable Type
0x0800 Alarm Type
0x1000 Trip Type
0x2000 Flexlogic Element
FC157 unsigned 16 bits LED Colour
0Off
1Red
2 Green
3Orange
FC161C unsigned 16 bits Motor Thermal Model Overload Curve
16 FlexCurve A
17 FlexCurve B
18 FlexCurve C
19 FlexCurve D
22 IEC
23 Motor
FC161D unsigned 16 bits Volts per Hertz Curve
7 Definite Time
16 FlexCurve A
17 FlexCurve B
18 FlexCurve C
19 FlexCurve D
24 Inverse A
25 Inverse B
26 Inverse C
FC161 unsigned 16 bits OC Curve Selection
0 IEEE Extr. Inverse
1 IEEE Very Inverse
2 IEEE Mod Inverse
Code Type Definition