11-308 869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE
FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP
0Modbus
1 IEC60870-5-103
2 DNP 3.0
FC210 unsigned 16 bits RS 485 Baud Rate
0 9600 baud
1 19200 baud
2 38400 baud
3 57600 baud
4 115200 baud
FC211 unsigned 16 bits RS 485 Parity
0None
1Odd
2Even
FC212 unsigned 16 bits ASDU Ident Type
03
19
FC217 unsigned 16 bits Ethernet Duplicate
0Discard
1Accept
FC218 unsigned 16 bits Ethernet Mode
1Full-Duplex
FC219 unsigned 16 bits Ethernet Port 4/5 Operation
0 Independent
1LLA
2PRP
FC220 unsigned 16 bits IRIG-B Signal Type
0None
1DC Shift
2 Amplitude Mod.
FC226 unsigned 16 bits WiFi Infrastructure Security
0None
1WPA2-PSK
FC228 unsigned 16 bits 61850 Status
0x0001 Comms NV OK
0x0002 Comms NV Done
0x0004 Comms V OK
0x0008 Comms V Done
0x0010 Main NV OK
0x0020 Main NV Done
0x0040 Main V OK
0x0080 Main V Done
0x0100 NR. Error CID
0x0200 R. Default CID
0x0400 R. Saving CID to Flash
0x0800 CID Handling Done
FC229 unsigned 16 bits DNP Analog Input Point Scale Factor
1 / 0.001
Code Type Definition