EasyManua.ls Logo

GE 869 - Page 45

GE 869
436 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 6: IEC 60870-5-104 INTEROPERABILITY
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 6-5
Table 6-5: Parameter in control direction
Table 6-6: File transfer
Type identifier and cause of transmission assignments (station-specific parameters) are
shown in the following tables. In these tables, shaded boxes () are not required, black
boxes () are not permitted in the companion standard, empty cells indicate the functions
or ASDU are not used, and a cross () indicates availability only in the standard direction.
Table 6-7: Cause of transmission numbers
Number / description Mnemonic
<110> := Parameter of measured value, normalized value PE_ME_NA_1
<111> := Parameter of measured value, scaled value PE_ME_NB_1
<112> := Parameter of measured value, short floating point value PE_ME_NC_1
<113> := Parameter activation PE_AC_NA_1
Number / description Mnemonic
<120> := File ready F_FR_NA_1
<121> := Section ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := Ack file, ack section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory (blank or X, available only in monitor [standard] direction) F_DR_TA_1
<127> := Query log - Request archive file F_SC_NB_1
Number Cause of transmission
1 Periodic, cyclic
2 Background scan
3 Spontaneous
4 Initialized
5 Request or requested
6 Activation
7 Activation confirmation
8 Deactivation
9 Deactivation confirmation
10 Activation termination
11 Return information caused by a remote command
12 Return information caused by a local command
13 File transfer
20 Interrogated by station interrogation
21 to 36 Interrogated by group <number> interrogation
37 Requested by general counter request
38 to 41 Requested by group <number> counter request
44 Unknown type of identification
45 Unknown cause of transmission
46 Unknown command address of ASDU
47 Unknown information object address

Other manuals for GE 869