CHAPTER 6: IEC 60870-5-104 INTEROPERABILITY
869 MOTOR PROTECTION SYSTEM – COMMUNICATIONS GUIDE 6-9
Counter freeze without reset.
Counter freeze with reset.
Counter reset.
General request counter.
Request counter group 1.
Request counter group 2.
Request counter group 3.
Request counter group 4.
Parameter loading:
Threshold value.
Smoothing factor.
Low limit for transmission of measured values.
High limit for transmission of measured values.
Parameter activation:
Activation/deactivation of persistent cyclic or periodic transmission of the addressed
object.
Test procedure:
Test procedure.
File transfer in monitor direction:
Transparent file.
Transmission of disturbance data of protection equipment.
Transmission of sequences of events.
Transmission of sequences of recorded analog values.
File transfer in control direction:
Transparent file.
Background scan:
Background scan.
Definition of timeouts:
Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s.
Maximum number of outstanding I-format APDUs (k) and latest acknowledge APDUs (w):
Maximum range of values k: 1 to 32767 (2
15
1) APDUs, accuracy 1 APDU.
Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU.
Recommendation: w should not exceed two-thirds of k.
Port number:
Parameter Default value Remarks Selected value
t
0
Timeout of connection establishment N/A
t
1
15 s Timeout of send or test APDUs 15 s
t
2
10 s Timeout for acknowledgements in case of no
data messages t
2
< t
1
10 s
t
3
20 s Timeout for sending test frames in case of a
long idle state
20 s
Parameter Default value Remarks Selected value
k 12 APDUs Maximum difference receive sequence number
to send state variable
12 APDUs
w 8 APDUs Latest acknowledge after receiving w I-format
APDUs
8 APDUs