LARGE CASSETTE TECHNICAL OVERVIEW
ENGLISH
Topic Title
E-10
DIP Switch Settings
Description
Capacity Room Card Running Mode Unit Type
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
Capacity: 24kBTU(7.1kW) ON ON OFF --- --- --- --- ---
Capacity: 30kBTU(9.0kW) OFF OFF ON --- --- --- --- ---
Capacity: 35kBTU(10.5kW) ON OFF ON --- --- --- --- ---
Capacity: 42kBTU(12.5kW) OFF ON ON --- --- --- --- ---
Capacity: 48kBTU(14.0kW_ ON ON ON --- --- --- --- ---
Room card invalid(default) --- --- --- OFF --- --- --- ---
Room card valid --- --- --- ON --- --- --- ---
Heat pump(default) --- --- --- --- OFF --- --- ---
Cooling only --- --- --- --- ON --- --- ---
High performance cassette --- --- --- --- --- OFF OFF ON
Indoor unit Address
(Indoor unit address for one wired
controller control more than one unit)
BM3-5 BM3-6 BM3-7 BM3-8
0 (master) OFF OFF OFF OFF
1 (slave) OFF OFF OFF ON
2 (slave) OFF OFF ON OFF
3 (slave) OFF OFF ON ON
4 (slave) OFF ON OFF OFF
5 (slave) OFF ON OFF ON
6 (slave) OFF ON ON OFF
7 (slave) OFF ON ON ON
8 (slave) ON OFF OFF OFF
9 (slave) ON OFF OFF ON
10 (slave) ON OFF ON OFF
11 (slave) ON OFF ON ON
12 (slave) ON ON OFF OFF
13 (slave) ON ON OFF ON
14 (slave) ON ON ON OFF
15 (slave) ON ON ON ON
BM1 DIP Switch Settings
Wired Controller Communication Address

Table of Contents

Other manuals for GE ASH220NCDW

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE ASH220NCDW and is the answer not in the manual?

GE ASH220NCDW Specifications

General IconGeneral
BrandGE
ModelASH220NCDW
CategoryHeat Pump
LanguageEnglish

Related product manuals