GE Multilin C60 Breaker Protection System 5-261
5 SETTINGS 5.8 INPUTS AND OUTPUTS
5
b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES
In a C60 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each
GOOSE message is programmed in the SETTINGS PRODUCT SETUP  COMMUNICATIONS  IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION TRANSMISSION  FIXED GOOSE  GOOSE ID setting.
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the SETTINGS PRODUCT SETUP  COMMUNICATIONS  IEC 61850 PROTOCOL GSSE/GOOSE
CONFIGURATION TRANSMISSION  GSSE  GSSE ID setting.
In C60 releases previous to 5.0x, these name strings were represented by the
RELAY NAME setting.