GE Multilin C60 Breaker Protection System 5-261
5 SETTINGS 5.8 INPUTS AND OUTPUTS
5
b) LOCAL DEVICES: ID OF DEVICE FOR TRANSMITTING GSSE MESSAGES
In a C60 relay, the device ID that represents the IEC 61850 GOOSE application ID (GoID) name string sent as part of each
GOOSE message is programmed in the SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL
GSSE/GOOSE CONFIGURATION TRANSMISSION FIXED GOOSE GOOSE ID setting.
Likewise, the device ID that represents the IEC 61850 GSSE application ID name string sent as part of each GSSE mes-
sage is programmed in the SETTINGS PRODUCT SETUP COMMUNICATIONS IEC 61850 PROTOCOL GSSE/GOOSE
CONFIGURATION TRANSMISSION GSSE GSSE ID setting.
In C60 releases previous to 5.0x, these name strings were represented by the
RELAY NAME setting.