3BB4 Field Output 1 Operate (6 items) 0 to 4294967295 --- 1 F300 0
3BC0 Field Output 1 Seal In (6 items) 0 to 4294967295 --- 1 F300 0
3BCC Field Output 1 Events (6 items) 0 to 1 --- 1 F102 1 (Enabled)
3BD2 ...Repeated for Field Contact Output 2
3C14 ...Repeated for Field Contact Output 3
3C56 ...Repeated for Field Contact Output 4
3C98 ...Repeated for Field Contact Output 5
3CDA ...Repeated for Field Contact Output 6
3D1C ...Repeated for Field Contact Output 7
3D5E ...Repeated for Field Contact Output 8
Field Unit Latching Outputs (Read/Write Setting) (8 modules)
3DC7 Field Latching Output 1 ID 0 to 1 --- 1 F205 "FLO Ux /LO"
3DCD Field Latching Output 1 Open 0 to 4294967295 --- 1 F300 0
3DCF Field Latching Output 1 Close 0 to 4294967295 --- 1 F300 0
3DD1 Field Latching Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)
3DD2 Field Latching Output 1 Reserved (2 items) 0 to 1 --- 1 F001 0
3DD4 ...Repeated for Field Latching Output 2
3DE1 ...Repeated for Field Latching Output 3
3DEE ...Repeated for Field Latching Output 4
3DFB ...Repeated for Field Latching Output 5
3E08 ...Repeated for Field Latching Output 6
3E15 ...Repeated for Field Latching Output 7
3E22 ...Repeated for Field Latching Output 8
Field Unit Shared Outputs (Read/Write Setting) (16 modules)
3E30 Field Shared Output 1 ID 0 to 65535 --- 1 F205 "SO 1"
3E36 Field Shared Output 1 Operate 0 to 4294967295 --- 1 F300 0
3E38 Field Shared Output 1 Unit Dest 1 0 to 8 --- 1 F256 0 (None)
3E39 Field Shared Output 1 Channel Dest 1 1 to 15 --- 1 F001 1
3E3A Field Shared Output 1 Unit Dest 2 0 to 8 --- 1 F256 0 (None)
3E3B Field Shared Output 1 Channel Dest 2 1 to 15 --- 1 F001 1
3E3C Field Shared Output 1 Events 0 to 1 --- 1 F102 1 (Enabled)
3E3D ...Repeated for Field Shared Output 2
3E4A ...Repeated for Field Shared Output 3
3E57 ...Repeated for Field Shared Output 4
3E64 ...Repeated for Field Shared Output 5
3E71 ...Repeated for Field Shared Output 6
3E7E ...Repeated for Field Shared Output 7
3E8B ...Repeated for Field Shared Output 8
3E98 ...Repeated for Field Shared Output 9
3EA5 ...Repeated for Field Shared Output 10
3EB2 ...Repeated for Field Shared Output 11
3EBF ...Repeated for Field Shared Output 12
3ECC ...Repeated for Field Shared Output 13
3ED9 ...Repeated for Field Shared Output 14
3EE6 ...Repeated for Field Shared Output 15
3EF3 ...Repeated for Field Shared Output 16
Field Unit RTDs (Read/Write Setting) (8 modules)
3F00 Field Unit RTD 1Name 0 to 1 --- 1 F205 "RTD 1"
3F06 Field Unit RTD 1 Origin 0 to 24 --- 1 F253 0 (None)
3F07 Field Unit RTD 1 Type 0 to 2 --- 1 F259 0 (100 Ohm
Nickel)
3F08 ...Repeated for Field Unit RTD 2
3F10 ...Repeated for Field Unit RTD 3
3F18 ...Repeated for Field Unit RTD 4
Table B–10: MODBUS MEMORY MAP (Sheet 20 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT