B
40BE DNP Other Default Deadband 0 to 100000000 --- 1 F003 30000
40C0 DNP IIN Time Synchronization Bit Period 1 to 10080 min 1 F001 1440
40C1 DNP Message Fragment Size 30 to 2048 --- 1 F001 240
40C2 DNP Client Address 3 0 to 4294967295 --- 1 F003 0
40C4 DNP Client Address 4 0 to 4294967295 --- 1 F003 0
40C6 DNP Client Address 5 0 to 4294967295 --- 1 F003 0
40C8 DNP Number of Paired Binary Output Control Points 0 to 32 --- 1 F001 0
40C9 DNP TCP Connection Timeout 10 to 7200 s 1 F001 120
40CA DNP Communications Reserved (22 items) 0 to 1 --- 1 F001 0
40E0 TCP Port Number for the IEC 60870-5-104 Protocol 0 to 65535 --- 1 F001 2404
40E1 IEC 60870-5-104 Protocol Function 0 to 1 --- 1 F102 0 (Disabled)
40E2 IEC 60870-5-104 Protocol Common Address of ASDU 0 to 65535 --- 1 F001 0
40E3 IEC 60870-5-104 Protocol Cyclic Data Transmit Period 1 to 65535 s 1 F001 60
40E4 IEC 60870-5-104 Current Default Threshold 0 to 100000000 --- 1 F003 30000
40E6 IEC 60870-5-104 Voltage Default Threshold 0 to 100000000 --- 1 F003 30000
40E8 IEC 60870-5-104 Power Default Threshold 0 to 100000000 --- 1 F003 30000
40EA IEC 60870-5-104 Energy Default Threshold 0 to 100000000 --- 1 F003 30000
40EC IEC 60870-5-104 Power Default Threshold 0 to1 --- 0.01 F001 100
40EE IEC 60870-5-104 Other Default Threshold 0 to 100000000 --- 1 F003 30000
40F0 IEC 60870-5-104 Client Address (5 items) 0 to 4294967295 --- 1 F003 0
4104 IEC 60870-5-104 Redundancy Port Enabled/Disabled 0 to 1 --- 1 F126 0 (No)
4105 Port 2 IP Address 0 to 4294967295 --- 1 F003 2130706433
4107 Port 2 IP Subnet Mask 0 to 4294967295 --- 1 F003 4278190080
4109 Port 2 Gateway IP Address 0 to 4294967295 --- 1 F003 56554497
410B PRT2 Ethernet Operation Mode 0 to 1 --- 1 F192 1 (Full-Duplex)
410C PRT2 Redundancy Enabled 0 to 2 --- 1 F627 0 (None)
410D Port 3 IP Address 0 to 4294967295 --- 1 F003 2130706433
410F Port 3 IP Subnet Mask 0 to 4294967295 --- 1 F003 4278190080
4111 Port 3 Gateway IP Address 0 to 4294967295 --- 1 F003 56554497
4113 Port 3 Ethernet Operation Mode 0 to 1 --- 1 F192 1 (Full-Duplex)
4114 PRT1 GOOSE Enabled 0 to 1 --- 1 F102 1 (Enabled)
4115 PRT2 GOOSE Enabled 0 to 1 --- 1 F102 1 (Enabled)
4116 PRT3 GOOSE Enabled 0 to 1 --- 1 F102 1 (Enabled)
4117 Default IPv4 Route 0 to 4294967295 --- 1 F003 2130706433
4119 PRT2 PRP Mcst Addr --- --- --- F072 0
411C IEC Communications Reserved (33 items) 0 to 1 --- 1 F001 0
413E High Enet Traffic Function 0 to 1 --- 1 F102 0 (Disabled)
413F High Enet Traffic Events 0 to 1 --- 1 F102 0 (Disabled)
4140 DNP Object 1 Default Variation 1 to 2 --- 1 F001 2
4141 DNP Object 2 Default Variation 1 to 3 --- 1 F001 2
4142 DNP Object 20 Default Variation 0 to 3 --- 1 F523 0 (1)
4143 DNP Object 21 Default Variation 0 to 3 --- 1 F524 0 (1)
4144 DNP Object 22 Default Variation 0 to 3 --- 1 F523 0 (1)
4145 DNP Object 23 Default Variation 0 to 3 --- 1 F523 0 (1)
4146 DNP Object 30 Default Variation 1 to 5 --- 1 F001 1
4147 DNP Object 32 Default Variation 0 to 5 --- 1 F525 0 (1)
4148 SCADA Protocol 0 to 2 --- 1 F629 0 (DNP 3.0)
Communications Actual Values (Read Only)
4160 Modbus Available TCP/IP Connections 0 to 4 --- 1 F001 4
4161 DNP Available TCP/IP Connections 0 to 2 --- 1 F001 2
4162 IEC Available TCP/IP Connections 0 to 2 --- 1 F001 2
4163 MMS Available TCP/IP Connections 0 to 5 --- 1 F001 5
4164 PMU Available TCP/IP Connections 0 to 4 --- 1 F001 4
Table B–10: MODBUS MEMORY MAP (Sheet 23 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE C60 and is the answer not in the manual?

GE C60 Specifications

General IconGeneral
BrandGE
ModelC60
CategoryRelays
LanguageEnglish

Related product manuals